Section Title
Product Specifications
SynapSoft™ 5.2 consists of three basic components; the SynapSense Wireless Network, the Console Application, and a browser-based User Interface. This system is a secure non-intrusive wireless system which does not require IP addresses or powered input for the sensor network and does not interfere with 802.11 WiFi networks.
Below is an example of a SynapSense installation in a data center rack.

Environmental Monitoring
ThermaNode™: Temperature/Humidity
Power Reqs 4 Energizer AA Lithium-Iron (L91) or line powered
Battery Life: 4-6yrs (typical)
Operating Temp: 0ºC to 50ºC (Indoor Use Only)
Warranty 1 year
Certification FCC Part 15, Subpart C. 15.247; Industry Canada;
CE Marking EN 300 328; V1.7.1
(2006-05) and EN 300 440-2 V1.1.2 (2004-07)
RF Specs 2.4GHz, ISM unlicensed band
IEEE 802.15.4 MAC
Data rate maximum: 250 Kbps
Maximum RF output power: 0dBm
RF Range: Typical 15m, Max 80m
Internal Sensed Data
Dew Point Sensor
Operating Range: 10ºC-35ºC, 20%RH - 80%RH
Accuracy: Nominal +0.5ºC-0.5ºC
Temperature Sensor
Accuracy: 10ºC-43ºC: ±0.3ºC
0ºC-10ºC & 43ºC-50ºC: ±0.7ºC
Time Constant: 230 seconds moving air (typical)
External Sensed Data
Up to 6 thermistors
Temperature Range: 0ºC-50ºC
Accuracy: ±0.3ºC
Operating Range: 0ºC-50ºC
Time Constant: 30 sec moving air; 60 sec static air (typical)
Pressure Node: Differential Air Pressure
Power Reqs: 4 Energizer AA Lithium-Iron (L91)
Differential Pressure Range: -500 to 500 Pa (-2.0 to 2.0" H2O)
Zero point accuracy: 0.5Pa (0.002" H2O)
Span Accuracy: ±0.3% of reading
Power & Current Metering
Constellation Node: 0 - 10V and 4-20mA
Power Requirements
4 Energizer AA Lithium-Iron (L91) or external 24VDC Power Adapter,
Provided for certain applications
110-240VAC (50~60Hz)
Analog Inputs
4 X 4-20mA: Accuracy: ±1.2% Full Scale
2 X 0-10V Accuracy: ±1.6% Full Scale
Electrical Energy Meter (Contact)
Measurement: 3 Phase, 208 to 480 VAC options,
Delta/”Y”, 50 or 60Hz
Current Specs: up to 2400amps per phase via Split Core CT's
Resolution: ±0.5kwh per hour non cumulative
Accuracy: ±1.0% Typical, ±2% Max (Full Scale)
Approvals: UL, CE
True RMS Current Sensor
Range: 0 - 200A RMS
Frequency: 50 - 60Hz
Accuracy: ±0.5%
Chilled Water Energy Meter
Installation: Non-intrusive chilled water energy monitoring
Range: 0 - 300 kWh/5 minutes
Dual and Single flow
Other Sensing
Particle Counter Measurement (4-20mA)
Particle size: 0.45 - 25Pm
Accuracy: ±1.8%
Counting Efficiency: 100% for particles > 0.75Pm (per JIS)
Rope Style Leak Detection System (Contact)
Available Lengths: Up to 1000 ft
SynapSense Gateway
Gateway Node
IP addressable to SynapSense Server
Power Reqs: External 5VDC Power Adapter, 110-240VAC (50~60Hz)
Ethernet Throughput: 256kbps
Ethernet Network Security via Lantronix
XportAR: Rijndael 128-bit encryption,
password protection, IP address filtering,
locking features, hardened OS and stack
Software & Database Components 
Typical Hardware Requirements
Processor Dual-core Intel® Xeon® (2.0 GHz, 1333MHz FSB) or equivalent
Memory 4 GB RAM
Disk Space: 500 GB (hot swap RAID1 preferred)
Connectivity 2 Gigabit Ethernet adaptersSoftware Requirements
Operating System Windows XP Pro (64-bit), Windows Server 2003/2008
User Privileges with full administrator privileges configured for installation.
Optional SNMP Version 2.0 or 3.0Client PC Requirements
Supported Browsers Internet Explorer 7.x or higher; Mozilla Firefox 2.x or higher
Flash Plug-in Adobe Flash Player 9.x or higher
Contact Us
Please contact a SynapSense Representative to learn more about SynapSoft 5.2™.
Internal Sensed Data
Temperature Sensor
External Sensed Data
Pressure Node: Differential Air Pressure
Constellation Node: 0 - 10V and 4-20mA
Electrical Energy Meter (Contact)
True RMS Current Sensor
Chilled Water Energy Meter