SynapSoft™ 5.3 consists of three basic components; the SynapSense Wireless Network, the Console Application, and a browser-based User Interface. This system is a secure non-intrusive wireless system which does not require IP addresses or powered input for the sensor network and does not interfere with 802.11 WiFi networks.
Below is an example of a SynapSense installation in a data center rack.

Environmental Monitoring
ThermaNode™:
Usage: Temp/Humidity/Dew Point
Internal Sensed Data
Dew Point Sensor
Operating Range: 10ºC-35ºC, 20%RH - 80%RH
Accuracy: Nominal +0.5ºC-0.5ºC
Temperature Sensor
Accuracy: 10ºC-43ºC: ±0.3ºC
0ºC-10ºC & 43ºC-50ºC: ±0.7ºC
Time Constant: 230 seconds moving air (typical)
External Sensed Data
Up to 6 thermistors
Temperature Range: 0ºC-50ºC
Accuracy: ±0.3ºC
Operating Range: 0ºC-50ºC
Time Constant: 30 sec moving air; 60 sec static air
Pressure Node:
Usage: Differential Air Pressure
Differential Pressure Range: -500 to 500 Pa (-2.0 to 2.0 H2O)
Zero point accuracy: ±0.5Pa (0.002 inH2O)
Span Accuracy: ±3% of reading
Power & Current Metering
Constellation Node:
Usage: Integration with 0 - 10V and 4-20mA inputs
Power: External 24VDC Power Adapter where applicable (110-240VAC, 50~60Hz)
Four 4-20mA analog inputs
Two 0-10V analog inputs
4-20mA Accuracy: ±1.2% Full Scale
0-10V Accuracy: ±1.6% Full Scale
Branch Circuit Monitoring
Usage: Circuit Level Metering
Capacity: Up to 84 branch circuits
Power Measurement: 50 and 100 amp CTs available
Configuration: Wall or subfloor mount
Accuracy: ±1.0% for current, ±3.0% for power
Power Sensing
Electrical Power Sensor
Measurement: 3 Phase, 208 to 480 VAC, 50/60Hz
Supports: Delta/Wye options
Current: Available CTs from 50 - 4000 amps
Accuracy: IEC 60687 Class 0.5/ANIS C12.20 0.5 compliant
Certifications: UL, CE
True RMS Current Sensor
Range: 0 - 200A RMS
Frequency: 50 - 60Hz
CT Accuracy: ±0.5%
Chilled Water Energy Meter
Usage: Volumetric flow, pipe temp
Range: 0 - 300 kWh/5 minutes
Dual and Single flow
Accuracy: Flow ±2.0%, pipe temperature ±0.6ºC, energy ±4.0%
Other Sensing
Particle Counter Measurement (4-20mA)
Particle size: 0.45 - 25Pm
Accuracy: ±1.8%
Counting Efficiency: 100% for particles > 0.75Pm (per JIS)
Rope Style Leak Detection System (Contact)
Available Lengths: Up to 1000 ft
Door Status (Contact)
Magnetic Sensor
Equipment Status (Contact)
Range: 1 - 150Amps
Frequency Range: 50 - 60Hz
SynapSense Gateway
Gateway Node
Ethernet Connectivity to server
Power: External 5VDC Power Adapter, 110-240VAC, (50~60Hz)
Ethernet Throughput: 256kbps
Security: Lantronix XportAR: Rijndael 128-bit encryption,
password protection, IP address filtering,
locking features, hardened OS and stack
Wireless Node Specifications
Power: 4 Energizer AA lithium-ion batteries (L91)
Typical Battery Life: 4-6 years
Operating Temp: 0ºC to 50ºC (Indoor Use Only)
Warranty: 1 year
Certification: FCC Part 15, Subpart C, 15.247; Industry Canada;
CE Marking EN 300 328; V1.7.1
(2006-05) and EN 300 440-2 V1.1.2 (2004-07)
Radio: 2.4GHz, ISM unlicensed band IEEE 802.15.4 MAC
Data rate maximum: 250 Kbps
Maximum RF output power: 0dBm
Typical RF Range: 15m
Maximum RF Range: 80m
Server and Client Specifications 
Minimum Server Requirements
Processor: X2 Quad-Core Xeon E5420 2.5 GHz or equivalent
Memory: 8GB RAM
Hard Drive: 500 GB
Connectivity: 2 Gigabit Ethernet adapters
OS Compatibility
Windows Server 2003 (32, 64-bit)
Windows Server 2008 (32, 64-bit)System Requirements
Email: SMTP server capable of sending alert notificationsClient PC requirements
Minimum Screen Resolution: 1280 x 1024
Browsers: IE 7.x or higher;
Mozilla Firefox 3.x or higher
Flash Plug-in: Adobe Flash Player 10.x or higher
Control Server
Hardware Requirements (Minimum)
Processor: Minimum 2.0 GHz
Memory: 2GB RAM
Server Hard Drive: 120 GB hard drive (dedicated for OS and SynapSense Software)
Additional 120 GB w/RAID-1 setting is recommended
Network: 2 Gigabit Network Adapters
DVD ROM drive [optional]
OS Compatibility
Operating System: MS Windows Server 2003 Service Pack 2
User Privileges: Administrator privileges required
Server Mode
Always On, Redundant Power Source
Contact Us
Please contact a SynapSense Representative to learn more about SynapSoft 5.3™.


Internal Sensed Data
Temperature Sensor
External Sensed Data
Pressure Node:
Constellation Node:
Power Sensing
True RMS Current Sensor
Chilled Water Energy Meter